WhatsApp

AL-E720 SINGLE PHASE PERCENTAGE BIASED DIFFERENTIAL PROTECTION RELAY TRAINER

Project Information

  • Category: ELECTRICAL ENGINEERING
  • Sub Category: POWER SYSTEM AND PROTECTION LAB
  • Model Number: AL-E720

Description

AL-E720 SINGLE PHASE PERCENTAGE BIASED DIFFERENTIAL PROTECTION RELAY TRAINER

DETAILED TECHNICAL SPECIFICATIONS

DIFFERENTIAL RELAY TESTING SYSTEM

Model No.: AL-E720

Quantity: 1 Set

Offered Brand: AMBEYLABS

Product Category: Electrical Protection and Relay Testing Equipment

-----------------------------------------------------------------------------------------------------------------------------------------

1. General Description

The Differential Relay Testing System is an advanced educational laboratory equipment designed for studying the operating principles, characteristics, and performance of differential protection relays used in electrical power systems.

The system is designed to provide practical training in differential protection, current comparison, relay operating characteristics, current setting, operating time measurement, and fixed-bias differential protection.

The complete system shall comprise a single-phase input power supply, single-phase step-down transformer, variable AC autotransformer (Variac), differential protection relay, digital measurement instruments, test terminals, electrical circuit diagram, and necessary connecting leads and safety accessories.

The complete assembly shall be mounted on a robust industrial-grade aluminium-profile workstation with an industrial grey front panel.

2. Detailed Technical Specifications

A. Input Power Supply Module

1.Input supply voltage: 230 V AC ±10%.

2.Frequency: 50 Hz.

3.Phase: Single Phase.

4.Main power ON/OFF switch.

5.MCB-based input protection.

6.Power indication lamp.

7.Proper input supply terminals.

8.Suitable overload and short-circuit protection.

9.Proper electrical earthing arrangement.

B. Single-Phase Transformer Module

1.Type: Single-phase step-down transformer.

2.Primary input voltage: 230 V AC.

3.Secondary output voltage: 24 V AC.

4.Rated output current: 3 A.

5.Transformer capacity: 72 VA.

6.Suitable for supplying the experimental circuits.

7.Properly insulated primary and secondary windings.

8.Separate primary and secondary connection terminals.

9.Clearly identified input and output terminals.

C. Single-Phase Variac Module

1.Type: Single-phase variable autotransformer.

2.Input voltage: 230 V AC.

3.Variable output voltage: 0–270 V AC.

4.Output current: 0–2 A.

5.Continuously adjustable output voltage.

6.Rotary voltage adjustment knob.

7.Digital AC voltage indication.

8.Digital AC current indication.

9.Separate output connection terminals.

10.  Suitable electrical protection arrangement.

D. Differential Protection Relay Module

1.Type: Differential Protection Relay.

2.Normal operating voltage: 110 V AC, 50 Hz.

3.Current setting range: 0.2 A to 0.8 A.

4.Operating time: 25 milliseconds.

5.Biasing arrangement: Fixed Type.

6.Adjustable current setting facility.

7.Relay operating and tripping arrangement.

8.Suitable relay contact output terminals.

9.Provision for demonstrating differential current protection.

10.  Suitable for studying electrical fault detection and protection principles.

E. Digital Measurement Module

The system shall include digital measurement facilities for monitoring electrical parameters.

1.Digital AC voltage meter.

2.Digital AC current meter.

3.Seven-segment LED display.

4.Clearly identified measurement sections.

5.Suitable measuring terminals.

6.Provision for monitoring voltage and current during experiments.

7.Properly insulated measurement connections.

F. Differential Relay Test Terminal Module

1.Separate primary current input terminals (I₁).

2.Separate secondary current input terminals (I₂).

3.Differential current measurement terminals.

4.Red and black safety connection sockets.

5.Clearly identified terminal markings.

6.Suitable for experimental current comparison.

7.Provision for connecting the relay testing circuit.

G. Circuit Diagram and Experimental Connection Panel

1.Printed electrical circuit diagram.

2.Input AC supply representation.

3.Variac connection representation.

4.Single-phase transformer connection representation.

5.Differential relay connection representation.

6.Primary and secondary current paths.

7.Differential current identification.

8.Clearly labelled electrical connection points.

3. Mechanical Construction

Industrial Aluminium Profile Workstation

1.Heavy-duty industrial-grade aluminium profile structure.

2.Silver-grey aluminium frame.

3.Industrial grey front panel.

4.Blue reinforced corner connectors.

5.Side-mounted carrying handles.

6.Stable base with adjustable supporting feet.

7.Proper mounting arrangement for all electrical components.

8.Durable and corrosion-resistant finish.

9.Clearly identified control and measurement sections.

10.  Compact tabletop laboratory design.

4. Experiments and Training Capabilities

The system shall facilitate the following practical experiments:

1.Study of differential protection relay construction and working principles.

2.Study of differential protection in electrical power systems.

3.Study of current comparison principles.

4.Measurement and analysis of differential current.

5.Study of differential relay current setting.

6.Verification of relay operating current.

7.Study of fixed-bias differential protection.

8.Measurement of differential relay operating time.

9.Study of relay tripping characteristics.

10.  Demonstration of transformer differential protection principles.

11.  Study of relay response under normal operating conditions.

12.  Study of relay operation under differential fault conditions.

13.  Study of electrical fault detection techniques.

14.  Study of protective relay applications in power systems.

15.  Practical demonstration of electrical protection schemes.

5. Standard Scope of Supply

Sr. No.

Description

Quantity

1

Complete Differential Relay Testing System

1 Set

2

Single-phase transformer (230 V / 24 V, 3 A)

1 No.

3

Single-phase Variac (230 V / 0–270 V, 0–2 A)

1 No.

4

Differential protection relay

1 No.

5

Digital AC voltage meter

1 No.

6

Digital AC current meter

1 No.

7

Input power supply module with MCB

1 Set

8

Differential relay test terminal module

1 Set

9

Electrical circuit diagram panel

1 No.

10

Electrical connecting leads

1 Set

11

Safety accessories and interconnections

1 Set

12

Operating and experiment manual

1 Set

6. Safety Features

1.Main power ON/OFF switch.

2.MCB-based input protection.

3.Overload and short-circuit protection.

4.Proper electrical earthing.

5.Insulated electrical connection terminals.

6.Protection for variable AC output.

7.Clearly marked input and output terminals.

8.Electrical warning labels.

9.Proper cable routing and management.

10.  Safe arrangement for laboratory experiments.

7. General Requirements

·  Complete equipment shall be supplied in ready-to-operate condition.

·  All electrical components shall be properly mounted and interconnected.

·  All terminals shall be clearly identified.

·  All necessary connecting leads and accessories shall be supplied.

·  Detailed operating instructions and experiment manuals shall be provided.

·  Installation, commissioning, and demonstration shall be included.

·  Warranty and after-sales technical support shall be provided.

8. Offered Product Details

Particulars

Offered Specification

Brand

AMBEYLABS

Model Number

AL-E720

Product Name

Differential Relay Testing System

Quantity

1 Set

Input Supply

230 V AC ±10%

Frequency

50 Hz

Phase

Single Phase

Transformer

230 V / 24 V AC, 3 A

Transformer Capacity

72 VA

Variac Input

230 V AC

Variac Output

0–270 V AC

Variac Current

0–2 A

Relay Type

Differential Protection Relay

Relay Normal Voltage

110 V AC, 50 Hz

Current Setting

0.2–0.8 A

Operating Time

25 ms

Biasing

Fixed Type

Dimensions

830 × 350 × 645 mm (W × D × H)

Construction

Aluminium Profile Workstation

Colour Scheme

Industrial Grey / Silver with Blue Connectors

Application

Electrical Protection and Relay Testing Laboratory

9. Important Technical Clarifications

Before final manufacturing and tender submission, verify the following:

·  The 24 V AC, 3 A transformer output and 110 V AC relay operating requirement are different ratings; the actual relay supply and test circuit must be designed accordingly.

·  Confirm whether the Variac output of 0–270 V AC is isolated or non-isolated. A standard Variac is generally an autotransformer and does not provide galvanic isolation.

·  Confirm the differential relay's actual current injection arrangement and operating time measurement method.

·  Ensure suitable current limiting and protection for all test connections.

Note: The above specification is prepared for Model AL-E720 based on the supplied technical particulars. Additional unprovided ratings have not been assumed.

Technical Details